Sensocon - Selectable Range Differential Pressure Transmitter
The Series DPT Multi-Range Differenetial Pressure Transmitter was designed specifically for the building automation and HVAC industry.
With field selectable ranges down to 0.1 inches w.c., this product is ideal for monitoring building pressure, static pressure, differential pressure, or air velocity and flow. The Series DPT Differential Pressure Transmitter also has jumper selectable outputs for 4-20 mA or 0-10 V and unit selection giving additional flexibility. For a virtually maintenance free transmitter, order the optional automatic zero and the transmitter will perform its own zero point maintenance. The Multi-Range Differential Pressure Transmitter also has an optional backlit LCD for giving local indication.
Active Questions & AnswersAsk a Question
There are no current Discussions
Pump Accessories Service ProvidersView All (3)
Documents & ManualsView All Documents
Features
There are no Features available.
General Specifications
There are no General Specifications available.
Additional Specifications
Maximum Pressure:
100 in w.c.
Media compatibility:
Dry air or non-aggressive gases
Accuracy:
Ranges < 0.5 in w.c. = +/- 0.01 in w.c.
Ranges ? 0.5 in w.c. = +/- 1.5%
includes thermal effects, linearity, hysteresis,
repeatability, and long term stability.
Temperature Ranges:
Compensated: 14° to 122°F
Operating: 14° to 122°F
Response Time:
0.8 - 4.0, jumper selectable
Power Supply:
24 VDC or VAC, +/- 10%
Output:
Voltage: 3-wire 0 - 10V or 0 - 5V, jumper selectable
Power Consumption: <1.0W
Minimum Resistance: 1kΩ
Current: 3-wire4 - 20mA
Power Consumption: <1.2W
Maximum Load: 500Ω
Enclosure Rating:
IP 54/ NEMA 3
Display:
3 ½" Digit LCD Backlit LCD
Electrical Connections:
Screw terminal block